Unit of Measure

Specifications

Brands

N/A Autonics USA

Type

N/A Safety

Direct Current (DC) Voltage

N/A 24 V

Allowable Voltage Range

N/A 85 to 110 V

Power Consumption

N/A 4 W

Input Current (On)

N/A ≥ 5 mA

Direct Current (DC) Input Voltage (On)

N/A ≥ 11 V

Input Current (Off)

N/A ≤ 1 mA

Direct Current (DC) Input Voltage (Off)

N/A ≤ 5 V

Input Time

N/A ≥ 50 ms

Feedback Start Time (Manual)

N/A ≥ 100 ms

Cable Length

N/A ≤ 100 m

Cable Capacitance

N/A ≤ 10 nF

Cable Resistance

N/A ≤ 100 Ω

Safety Output

N/A Relay (A Contact)

Sub Output

N/A 1 x Positive Negative Positive (PNP) Transistor: X1

Instantaneous

N/A 4 x

Direct Current (DC) Capacity

N/A 5 A

Alternating Current (AC) Capacity

N/A 5 A

Alternating Current (AC) Voltage Capacity

N/A 240 V

Direct Current (DC) Voltage Capacity

N/A 30 V

Mechanical Life Expectancy

N/A ≥ 10000000 Operations

Malfunction Life Expectancy

N/A = 50000 Operations

Contact Resistance

N/A ≤ 100 mΩ

Inductive Load Switching

N/A IEC60947-5-1: AC-15 (230 V/2 A)

Conditional Short Circuit Current

N/A 100 A

Maximum Load Current

N/A 100 mA

Leakage Current

N/A ≤ 0.1 mA

International Standards

N/A European Standard (EN) International Organization for Standardization (ISO) 13849-1 (Category 4, PLe) Underwriter Laboratories (UL) Listed E249635 International Electrotechnical Commission (IEC)/European Standard (EN) 61508 (Safety Integrity Level (SIL)3) International Electrotechnical Commission (IEC)/European Standard (EN) 62061 (Safety Integrity Level (SIL) CL3) International Electrotechnical Commission (IEC)/European Standard (EN) 60947-5-1

Approval

N/A European Conformity (CE) S-Mark Certification Technical Inspection Association (TUV NORD) Underwriter Laboratories (UL) Listed

Shipping Weight

N/A 160 g

Unit Weight

N/A 110 g

Weight

N/A 0.2 lb