Power Supply, Din Rail mounting, Switching, 24 VDC output ,240 Watts, 10 Amp 100-240 VAC Input
Unit of Measure

Specifications

Brands

N/A Autonics USA

Output Power

N/A 240 W

Alternating Current (AC) Input Voltage

N/A 100 to 240 V

Alternating Current (AC) Input Frequency

N/A 50 Hz60 Hz

Alternating Current (AC) Permissible Voltage

N/A 85 to 264 V

Alternating Current (AC) Permissible Frequency

N/A 50 Hz60 Hz

Direct Current (DC) Permissible Voltage

N/A 120 to 370 V

Mounting

N/A German Institute of Standardization (DIN) Rail

Protection

N/A Inrush Current Output Low-Voltage Indicate Output Short-Circuit Over-Current Over-Voltage Power Factor Correction Remote Control Terminal Cover

Approval

N/A European Conformity (CE) Underwriters Laboratory for Canada and United States (cULus) Listed

Input Frequency

N/A 50 Hz60 Hz

Input Efficiency at 100 Volt (V) Alternating Voltage (AC) Voltage

N/A 0.89 %

Input Efficiency at 240 Volt (V) Alternating Voltage (AC) Voltage

N/A 0.92 %

Minimum Input Power Factor

N/A 0.9 %

Input Current Consumption at 100 Volt (V) Alternating Voltage (AC) Voltage

N/A 2.71 A

Input Current Consumption at 240 Volt (V) Alternating Voltage (AC) Voltage

N/A 1.12 A

Maximum Voltage Adjustment Range (±)

N/A 0.5 %

Maximum Input Fluctuation Ratio (±)

N/A 1 %

Maximum Load Fluctuation Ratio (±)

N/A 1 %

Maximum Ripple and Ripple Noise

N/A 1 %

Protection Structure

N/A Ingress Protection (IP) 20 (International Electrotechnical Commission (IEC) Standard)

Environment Ambient Temperature

N/A -10 to 50 ºC

Environment Storage Temperature

N/A -25 to 65 ºC

Maximum Surrounding Air Temperature

N/A 40 ºC

Environment Ambient Relative Humidity (RH)

N/A 25 to 85 %

Environment Storage Relative Humidity (RH)

N/A 25 to 90 %

Approximate Weight

N/A 866 g

Approximate Net Weight

N/A 736 g

Weight

N/A 1 lb

Switching Power Supply

Direct Current (DC) Output Voltage

N/A 24 V

Output Current

N/A 10 A

Note

Note

N/A
  • It is for 100 % load.
  • The output voltage adjuster (V.ADJ) should be used within voltage adjustment range.
  • It is for the rated input voltage 100-240VAC (85-264VAC), and 100% load.
  • It is for the rated input voltage 100-240VAC.
  • The weight includes packaging. The weight in parenthesis is for unit only.
  • Environment resistance is rated at no freezing or condensation.