Unit of Measure

Specifications

Brands

N/A Autonics USA

Number of Phase

N/A 3

Rated Load Alternating Current (AC) Voltage

N/A 220 V

Rated Load Current

N/A 100 A

Output Range Phase Control

N/A 0 to 98 %

Output Range Z.C. Control

N/A 0 to 100 %

Output Range On/Off Control

N/A 0 %100 %

Alternating Current (AC) Voltage Range

N/A 100 to 240 V

Frequency

N/A 50 Hz60 Hz

Minimum Load Current

N/A 1 A

Allowable Voltage Range

N/A 90 to 110 V

Maximum Alternating Current (AC) Voltage

N/A 32 V

Display Method

N/A 3-Digit 7-Segment Light-Emitting Diode (LED)

Approval

N/A European Conformity (CE)

Digital Inputs

N/A Automatic/Manual Switching Reset Run/Stop Switching

Output Alarm Alternating Current (AC) Voltage

N/A 250 V

Output Alarm Current

N/A 3 A

Output Alarm Direct Current (DC) Voltage

N/A 30 V

Output Communication

N/A RS485 Communication Output (Modbus RTU Method)

Setting Type

N/A By Front Keys, by Communication

Function Alarm

N/A Fuse Break Alarm Heater Break Alarm Heatsink Overheat Alarm Overcurrent Alarm Overvoltage Alarm Silicon Controlled Rectifier (SCR) Error Alarm

Cooling Method

N/A Forced Air Cooling (With the Cooling Fan)

Insulation Resistance

N/A Over 200 MΩ

Dielectric Strength

N/A 2000 VAC, 50/60 Hz for 1 min (Between Input Terminals and Power Terminals)

Output Leakage Current

N/A 10 mA

Noise Immunity

N/A ±2 kV the Square Wave Noise (Pulse Width: 1µs) by the Noise Simulator

Memory Protection

N/A Approximate 10 years (Non-volatile Semiconductor Memory Type)

Vibration

N/A 0.75 mm Amplitude at Frequency of 5 to 55Hz (for 1 min) in Each X, Y, Z Direction for 2 Hours

Vibration Malfunction

N/A 0.5 mm Amplitude at Frequency of 5 to 55 Hz in Each X, Y, Z Direction for 10 min

Environment Ambient Temperature

N/A -10 to 55 ºC

Environment Storage Temperature

N/A 20 to 80 ºC

Environment Ambient Relative Humidity (RH)

N/A 35 to 85 %

Environment Storage Relative Humidity (RH)

N/A 35 to 85 %

Shipping Weight

N/A 9.7 kg

Unit Weight

N/A 8.7 kg

Weight

N/A 0.2 lb

Control Method

Control Method

N/A
  • Phase control: Normal control mode
  • Cycle control: Fixed cycle control mode
  • On/Off control

Load

Load

N/A
  • Phase control, On/Off control: resistance load, inductive load
  • Cycle control: resistance load

Control Input

Control Input

N/A
  • Auto control: DC 4 to 20 mA, 1 to 5 VDC, On/Off contact (no-voltage input), pulse voltage (5 to 12 VDC)
  • Manual control: outside adjuster (10 kΩ), inside adjuster (output limit)

Indicator

Indicator

N/A
  • Operation indicator/Manual control indicator: green LED
  • Alarm indicator/output indicator/unit (V, A) indicator: red LED

Output Accuracy

Output Accuracy

N/A
  • Normal control: within ±10% F.S. of rated load voltage ,
  • Static current feedback control: within ± 3% F.S. of rated load current ,
  • Static voltage feedback control: within ± 3% F.S. of rated load voltage ,
  • Static power feedback control: within ± 3%

Function

Function

N/A Output limit (OUT ADJ), AUTO/MAN selection, control method selection, RESET, SOFT START, SOFT UP/DOWN, output high/low limit, input correction, input slope correction, monitoring (control input, load voltage/current/power/resistance, power supply frequency

Accessories

Accessories

N/A 11-Pin Connector
Isolating Barrier: 4