Bar Graph Temp Controller, DIN W48xH96mm, Heating or Cooling, Selectable Output (Relay, Current,…
Unit of Measure

Specifications

Brands

N/A Autonics USA

Width

N/A 48 mm

Height

N/A 96 mm

Alternating Current (AC) Voltage

N/A 100 to 240 V

Frequency

N/A 50 Hz60 Hz

Input Type Resistance Temperature Detector (RTD)

N/A Cu100Ω Cu50Ω DPt100Ω DPt50Ω JPt100Ω Nikel120Ω (6 types)

Input Type TC

N/A B C E G J K L N PLII (13 types) R S T U

Input Type Analog Voltage

N/A 0 to 10 V 0 to 100mV 0 to 5 V 1 to 5 V

Input Type Analog Current

N/A 0 to 20mA 4 to 20mA

Control Method

N/A On/Off Control P PD PI PID Control

Sampling Cycle

N/A 50 ms

Protection Structure

N/A Ingress Protection (IP) 65 (Front Panel)

The Number of Control Output

N/A 1 Output Type (Heating or Cooling Type)

Control Output

N/A Current Output Selectable Relay Output SSR Drive Output

Input/Output Option

N/A None

Approval

N/A European Conformity (CE)

Environment Ambient Temperature

N/A -10 to 50 ºC

Environment Storage Temperature

N/A -20 to 60 ºC

Environment Ambient Relative Humidity (RH)

N/A 35 to 85 %

Environment Storage Relative Humidity (RH)

N/A 35 to 85 %

Size

N/A 48 x 96 mm

Number of Control Output

N/A 1 (Heating or Cooling)

Control Output Type

N/A Relay, Current, SSR drive

Shipping Weight

N/A 160 g

Unit Weight

N/A 230 g

Weight

N/A 0.56 lb

Note

N/A
  • The 1 output type is heating or cooling output type and the 2 output type is heating and cooling output type.
  • The 1 output type is able to use only one output among relay output, current output, SSR drive output.
  • OUT1 of the 2 output type is fixed as heating output and OUT2 of the 2 output type is fixed as cooling output.
  • If you select the SSR drive output or current output model, you can select the appropriate control output.
  • Display accuracy:
  • At room temperature (23 ±5)
  • TC K, J, T, N, E type, below -100? / L, U, PL, RTD Cu50, DPt50: (PV ±0.3% or ±2, select the higher one) ±1digit
  • TC C, G and R, S type, below 200?: (PV ±0.3% or ±3, select the higher one) ±1digit
  • TC B type, below 400, there is no accuracy standards.
  • Out of room temperature range
  • RTD Cu50, DPt50: (PV 0.5% or ±3, select the higher one) ±1digit
  • RTD R, S, B, C, G: (PV ±0.5% or ±10, select the higher one) ±1digit
  • Other sensors: below -100, within ±5
  • The weight includes packaging. The weight in parenthesis is for unit only.
  • Environment resistance is rated at no freezing or condensation.